NCCER Electric-3 Mod-1 Flashcards | StudBud
Explore
/
NCCER Electric-3 Mod-1
NCCER Electric-3 Mod-1
25 terms
·
StudBud Administration
·
368 plays
Module 26301-‐17 Load Calculations - Branch and Feeder Circuits
Flashcards
25 cards
F
Practice quiz
P
Host live
L
Questions
25
Answers
1
load center length(LCL) for a circuit with (NC) loads of 20A at 60' and 50A at 125' from the source
125.12'
157.95'
106.43'
136.56'
2
Accordin to the NEC®, the total load of show windows must be calculated at not less than _____.
50VA per linear foot of show window
100VA per linear foot of show window
150VA per linear foot of show window
200VA per linear foot of show window
3
The load for 10' of multi-outlet assembly used to supply several loads simultaneously is
1800VA
3500VA
1980VA
2200VA
4
Air conditioning overcurrent devices can't exceed what % of the motor-rated load or the branch circuit selection current
225%
175%
300%
150%
5
Total ampacity for a 120V circuit W/ 4 Rec. rated NC duty and 6 Rec. rated continuous duty?
18.75A
17.25A
15A
16.5A
6
What is the motor full-load current for a motor with a nameplate rating of 50hp, 460V, 3Ø?
130A
52A
81A
65A
7
What is the feeder load (in VA) for three small appliance branch circuits?
1500VA
1800VA
2400VA
4500VA
8
Conductors must be derated when installed in conduit _____.
underneath roadways
on or above rooftops
in garages
in wet locations
9
LCL for circuit with the following NC loads: 125A @ 80' - 75A @ 110' - 50A @ 100'
93'
92'
94.6'
95.1'
10
Continuous loads are calculated at what percentage of the maximum current rating of the overcurrent device?
90%
100%
75%
80%
11
The demand load for four pieces of commercial cooking equipment is _____.
65%
80%
70%
90%
12
LCL for 208V, 4-wire, 3-phase circuit with fixed NC loads 60A @ 45' - 40A @ 55' - 30A @ 75' - 25A @ 100'
85.21'
60.40'
71.72'
63.55'
13
Resistance welders, the rating of the overcurrent device can't exceed what % of the primary current rating of the welder
300%
200%
125%
185%
14
What is the current capacity for No. 6 THWN aluminum conductor in conduit run through ambient temperature of 38°C?
45.5A
50A
44A
41A
15
What is the total load required by the NEC® for two appliance branch circuits plus a laundry branch circuit?
1500VA
4500VA
3000VA
6000VA
16
The maximum size dual-element fuse for a 40hp, 3Ø, 460V motor with a Design Letter D is
100A
175A
125
60A
17
NEC® requires that branch circuit conductors be derated when more than how many current-carrying conductors in a raceway
2
4
5
3
18
A noncontinuous load of two 120V outlets for heavy-duty lamp holders would have a load of
240VA
236VA
1200VA
600VA
19
What is the demand load for one household range with a nameplate rating of 11.75kW, 240V, 1Ø?
12kW
8kW
19kW
9kW
20
When space heating equipment uses electric resistance heating elements, protection for the elements must not exceed_____
30A
40A
50A
60A
21
The lighting load on a 120V circuit for 6 100W lights and 4 ballast with a rating of 1.5A, all are continuous for 8hrs
13.75A
10.50A
11.20A
15.60A
22
The voltage drop for a 100', 120V, two-wire, copper circuit, of 6,530 circular mils with a noncontinuous load of 13A?
4.01V
6.24V
3.28V
5.14V
23
What is the required circuit ampacity of a noncontinuous(NC), single-phase load of 8.5kW at 277V?
25.25A
28.15A
30.69A
17.32A
24
What is the ampacity of a water heater with a nameplate rating of 7,200VA at 240V?
30A
42.5A
32.5A
37.5A
25
A sign load cannot exceed how much of the branch circuit rating
80%
50%
100%
150%