Med gas quiz 4 Flashcards | StudBud
Explore
/
Med gas quiz 4
Med gas quiz 4
30 terms
·
StudBud Administration
·
660 plays
Imported from external platform
Flashcards
30 cards
F
Practice quiz
P
Host live
L
Questions
30
Answers
1
Category 1 medical-surgical vacuum sources shall consist of an automatic means to prevent__through any offcycle vacuum..
All of the above
Back pressure
Backflow
Vacuum
2
A category 1 dedicated WAGD source shall consist of__or more producers, each shall be sufficient to serve the peak..
3
All of the above
2
1
3
Vacuum filtration shall be located on the__side of the vacuum producer.
Upstream
All of the above
Downstream
Patient side
4
Category 1 medical-surgical vacuum systems shall activate which alarm when the backup or lag pump is running?
Master
All of the above
Local
Area
5
When the medical surgical vacuum pump(s) in operation is(are) incapable of adequately maintaining the required vacu..
None of the above
Manually or automatically
Manually
Automatically
6
Vacuum filtration shall be at least__to allow 1 filter to be exchanged without impairing the vacuum system.
As many as you want
No requirements
Duplex
Simplex
7
A WAGD source system shall activate the__alarm when the backup or lag producer is running.
Area
Local and master
Master
Local
8
Vacuum producers(e.g., fans or blowers) designed for operations at vacuum below 130mm(5inch)HgV shall be as follows.
Any of the above
Interconnected via piping
Ductwork
Determined by the manufacture
9
Vacuum exhausts from multiple pumps joined together to one common exhaust shall be permitted provided each pump can be..
Any of the above
Blind flange
Check valve
Manual valve
10
Vacuum receivers shall be capable of withstanding a gauge vacuum of__inches of mercury.
All of the above
29”
29.9”
30”
11
If the WAGD system is joined with the medical surgical vacuum piping, it shall be connected at a minimum distance of..
6
5
5.5
3
12
For each oxygen concentrator a local alarms to indicate low oxygen concentration when a concentration lower than_% is ob
91
95
93
99
13
Multiple vacuum pumps shall be permitted to be joined together to 1 common exhaust provided the common exhaust sized to.
Minimize back pressure
Manufactured recommendations
Prevent backflow
Peak calculated demand
14
Additional WAGD producers shall be__activated when the producer(s) in operation is(are) incapable of maintaining the..
None of the above
Either a or b
Manually
Automatically
15
Vacuum filtration shall be sized for__percent of the peak calculated demand while 1 filter or filter bundle is isolated.
99
95
100
90
16
The medical-surgical vacuum exhaust shall be turned down and screened. The screening shall be fabricated using what type
Steel mesh
Any of the above
Any non corroding material
Steel wire
17
Category 1 medical-surgical vacuum sources shall, at a minimum, consist of__or more vacuum pumps.
4
1
2
3
18
The monitor shall be capable of monitoring__% oxygen concentration with 1% accuracy.
95
93
99
97
19
On an oxygen for each concentrator unit used in the oxygen central supply system, an alarm indicating that oxygen..
Local alarm
Area alarm
Local and master alarm
Master alarm
20
To determine the type of WAGD sources and systems shall be chosen by consultation with__having knowledge of the req..
Medical staff
Maintenance staff
Verifier
Engineer
21
Use of oxygen concentrator supply system as all three sources shall only be permitted after documented risk analysis..
AHJ
Not allowed
Governing authority
Governing body
22
The medical surgical vacuum receiver shall be made serviceable without shutting down the system by__.
An isolation valve where tee’d into main line
Being valved at the end of the main line
A three valve bypass
Any method to ensure continuation of service
23
WAGD vacuum producers designed for operation at vacuums below__inches Hg/V shall be used only for WAGD service and not..
2”
5”
4”
3”
24
The vacuum exhaust shall be at least__ft from any doors, windows, air intake and shall NOT discharge in a place of publi
20ft
25ft
10ft
15ft
25
The WAGD source shall be permitted to be located near the__.
Outlets
Exhaust
Inlets
Intakes
26
Filters shall be efficient to__and 99.7% HEPA or better, per DOE-STD-3020
0.02
0.05
0.3
0.01
27
Oxygen concentrator supply units for use with medical gas pipelines shall produce oxygen meeting the requirements of?
Oxygen USP
Oxygen 93 USP
Medical air USP
Both a and c
28
What source shall not be used to power the Venturi of a WAGD system?
All of the above
Inert gas
Medical air
Instrument air
29
If WAGD is produced by the medical surgical vacuum source, the total concentration of oxidizers of oxygen(%O2) shall..
21.5%
15.5%
19.5%
23.6%
30
Medical surgical vacuum receivers shall be made of what kind of materials__?
Ferrous
Non ferrous
Deemed by the manufacturer
All of the above